| Type of current
|
Utilization category
|
Typical applications:
I = switch-on current,
Ic = Switch-off current,
Ie = Rated operational current,
U = voltage,
Ue = Rated operational voltage,
Ur = Recovery voltage
|
Verification of switching capacity
|
||||||||||||||||
| Switch on
|
Switch off
|
||||||||||||||||||
| |
|
|
|
|
|
cos φ
|
|
|
|
|
cos φ
|
||||||||
| Alternating current
|
AC-20 A(B)1)
|
Making and breaking without load
|
All values
|
|
1)
|
|
|
|
1)
|
1)
|
|
|
|
1)
|
|||||
| AC-21 A(B)1)
|
Switching resistive loads including low overloads
|
All values
|
|
1.5
|
|
1.05
|
|
0.95
|
1.5
|
|
1.05
|
|
0.95
|
||||||
| AC-22 A(B)1)
|
Switching mixed resistive and inductive loads including low overloads
|
All values
|
|
3
|
|
1.05
|
|
0.65
|
3
|
|
1.05
|
|
0.65
|
||||||
| AC-23 A(B)1)
|
Switching motors and other highly inductive loads
|
Ie ≤100
Ie > 100
|
|
10
10
|
|
1.05
1.05
|
|
0.45
0.35
|
8
8
|
|
1.05
1.05
|
|
0.45
0.35
|
||||||
| |
|
|
|
|
|
|
L/R
ms
|
|
|
|
|
L/R
ms
|
|||||||
| Direct current
|
DC-20 A(B)1)
|
Making and breaking without load
|
All values
|
|
1)
|
|
1)
|
|
1)
|
1)
|
|
1)
|
|
1)
|
|||||
| DC-21 A(B)1)
|
Switching resistive loads including low overloads
|
All values
|
|
1.5
|
|
1.05
|
|
1
|
1.5
|
|
1.05
|
|
1
|
||||||
| DC-22 A(B)1)
|
Switching mixed resistive and inductive loads, including low overloads (e.g. shunt motors)
|
All values
|
|
4
|
|
1.05
|
|
2.5
|
4
|
|
1.05
|
|
2.5
|
||||||
| DC-23 A(B)1)
|
Switching highly inductive loads (e.g. series motors)
|
All values
|
|
4
|
|
1.05
|
|
15
|
4
|
|
1.05
|
|
15
|
||||||
| 1) A: Frequent operation, B: Occassional operation.